I. General
388.1 |
Scope |
388.2 |
Definition |
A nonmetallic raceway with its associated fittings mounted to the surface of a structure.
388.6 |
Listing Requirements |
II. Installation
388.10 |
Uses Permitted |
This can be used in dry locations. It can be used to pass transversely through dry walls, dry partitions, and dry floors if it is unbroken. You must maintain access to the conductors on either side of the wall floor or partition.
388.12 |
Uses Not Permitted |
It cannot be installed concealed except as permitted in 388.10(2), where it might be damaged, where the voltage between conductors is 300 V or more unless so listed, in hoistways, in any hazardous area location except Class I, Division 2 permitted in 501.4(B), Exception, if ambient temperatures are higher than that for which the raceway is listed, or for conductors with insulation temperatures higher than the raceway is listed.
388.21 |
Size of Conductors |
Not larger than the raceway design calls for.
388.22 |
Number of Conductors or Cables |
Number not larger than the raceway design calls for. Cables can be installed if not prohibited by cable articles.
388.56 |
Splices and Taps |
388.60 |
Grounding |
388.70 |
Combination Raceways |
III. Construction Specifications
388.100 |
Construction |
It is made of nonmetallic material that is resistant to moisture, chemical atmospheres, impact and crushing, distortion from heat, and low temperatures. It is also flame-retardant.
388.120 |
Marking |
Article 90 Introduction
General
Wiring and Protection
Wiring Methods and Materials
Equipment for General Use
Special Occupancies
Special Equipment
Special Conditions
Tables
Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size
Annex D. Examples
Annex E. Types of Construction