I. General
350.1 |
Scope |
350.2 |
Definition |
This conduit is similar to flexible metal conduit, but it has a jacket over the metal conduit. The jacket is liquidtight, nonmetallic, and sunlight-resistant.
350.6 |
Listing Requirements |
II. Installation
350.10 |
Uses Permitted |
This conduit can be installed exposed or concealed, directly buried in earth and if protection from liquids, vapor, or solids is necessary or if flexibility is desired. It can be installed in hazardous areas if approved for that installation. Refer to Sections 501.4(B), 502.4, 503.3, 504.20, and 553.7(B).
350.12 |
Uses Not Permitted |
It cannot be installed when subject to damage or where temperatures exceed that which is approved for the material.
350.20 |
Size |
Minimum metric designator 16 (trade size ½). For exceptions, refer to Section 348.20(A). The maximum size allowed is metric designator 103 (trade size 4). Refer to 300.1(C) for metric designators and trade sizes.
350.22 |
Number of Conductors or Cables |
(A) Metric Designators 16 through 103 (Trade Sizes ½ through 4). Refer to Table 1, Chapter 9. Cables can be used if not prohibited by cable articles. Cables cannot exceed the fill requirements of Table 1, Chapter 9.
(B) Metric Designator 12 (Trade Size 3/8). Refer to the Fittings Outside Conduit columns in Table 348.22.
350.24 |
BendsHow Made |
Bends must not damage the conduit and must not reduce the internal diameter of the conduit. Bends can be made with auxiliary equipment manually. The radius of the curve to the centerline can not be less than that shown in Table 2, Chapter 9. Use the "Other Bends" column.
350.26 |
BendsNumber in One Run |
The maximum that is permitted is not more than 360° in bends between pull points.
350.30 |
Securing and Supporting |
It must be supported and secured not more than 1.4 m (4½ ft.) apart. It must be securely fastened within 300 mm (12 in.) of a conduit termination. Four exceptions are for when the conduit is fished, where flexibility is needed, length not exceeding 900 mm (3 ft.) at terminals, lengths not exceeding 1.8 m (6 ft.) from a fixture terminal connection for tap conductors to a lighting fixture as noted in Section 410.67(C) and within accessible ceilings for lengths not exceeding 1.8 m (6 ft.) from the last point where the raceway is fastened, for connections to luminaires or other equipment. Horizontal runs allowed to be supported by the openings in framing members not more than 1.4 m (4½ ft.) apart and fastened within 300 mm (12 in.) of a termination.
350.42 |
Couplings and Connectors |
350.56 |
Splices and Taps |
They can be made only in accordance with Section 300.15.
350.60 |
Grounding and Bonding |
This type of conduit can be used as a means of grounding under certain conditions. Refer to the NEC®.
III. Construction Specifications
350.120 |
Marking |
Article 90 Introduction
General
Wiring and Protection
Wiring Methods and Materials
Equipment for General Use
Special Occupancies
Special Equipment
Special Conditions
Tables
Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size
Annex D. Examples
Annex E. Types of Construction