I. General
501.1 |
Scope |
501.5 |
General |
This article refers to those areas classified as Class I in Section 500.5.
II. Wiring
501.10 |
Wiring Methods |
(A) Class I, Division 1. Only threaded rigid metal conduit, threaded steel intermediate conduit, or Type MI cable can be used. Boxes and fittings must be approved for Class I, Division 1. At least five threads must be engaged. MI cable has to be installed to prevent stress at the terminations. There is one exception. There are also requirements for industrial establishments with the use of MC-HC and ITC-HC cable.
(B) Class I, Division 2. Methods permitted are threaded rigid metal conduit; threaded steel intermediate metal conduit; enclosed gasketed busways; enclosed gasketed wire-ways; Type MI, MC, MV, or TC cable with approved terminations; Type PLTC cable; type ITC cable as permitted in 727.4 and all methods permitted in 501.10(A). Explosion-proof boxes or fittings are not required. Additional requirements and exceptions are noted.
501.15 |
Sealing and Drainage |
Seals must be provided and approved items must be used.
(A) Conduit Seals, Class I, Division 1
(B) Conduit Seals, Class I, Division 2
(C) Class I, Divisions 1 and 2. These are general rules.
(D) Cable Seals, Class I, Division 1
(E) Cable Seals, Class I, Division 2
(F) Drainage. In certain cases drainage of accumulated liquid is permitted and even required. Special requirements must be followed.
501.20 |
Conductor Insulation, Class I, Divisions 1 and 2 |
If the conductors come in contact with condensed vapors or liquids, the insulation must be identified for this use or have protection provided by a lead sheath or another approved sheath.
501.25 |
Uninsulated Exposed Parts, Class I, Divisions 1 and 2 |
There can be no uninsulated exposed parts such as conductors, buses, etc., that operate at more than 30 volts. This limit is reduced to 15 volts in wet locations. The protection must be in accordance with 500.7(E), 500.7(F), or 500.7(G).
501.30 |
Grounding and Bonding, Class I, Divisions 1 and 2 |
Wiring and equipment must be grounded in accordance with Article 250. Bonding jumpers with proper fitting or other approved means of bonding must be used. Locknut bushings and double locknut types of contacts are not acceptable. The means of bonding applies to all raceways, fittings, boxes, enclosures, etc., between Class I locations and the grounding point for service equipment or separately derived systems. If flexible conduit is used it must have internal or external bonding jumpers in parallel with each conduit. It must also comply with the requirements of Section 250.120 where flexible metal or liquidtight flexible metal conduit is used. There are exceptions.
501.35 |
Surge Protection |
501.40 |
Multiwire Branch Circuits |
III. Equipment
501.100 |
Transformers and Capacitors |
(A) Class I, Division 1
(B) Class I, Division 2. In these locations they must be in accordance with Sections 450.21 through 450.27.
501.105 |
Meters, Instruments, and Relays |
(A) Class I, Division 1. They must be in Class I, Division 1 enclosures.
(B) Class I, Division 2
501.115 |
Switches, Circuit Breakers, Motor Controllers, and Fuses |
(A) Class I, Division 1. Must be in an enclosure and the entire assembly must be identified for Class I locations.
(B) Class I, Division 2
501.120 |
Control Transformers and Resistors |
Transformers, impedance coils, and resistors are covered by this section.
(A) Class I, Division 1. In this location they must have enclosures identified for Class I, Division 1.
(B) Class I, Division 2. In this location switching mechanisms must be in accordance with Section 501.6(B). General-purpose enclosures can be used for coils and windings. Resistors must have enclosures identified for Class I locations. If the resistor is fixed and the maximum operating temperature is not more than 80% of the ignition temperature of the gas or vapor, a general-purpose enclosure can be used.
501.125 |
Motors and Generators |
(A) Class I, Division 1. In this location they must be either identified for Class I, Division 1 locations or be totally enclosed with a positive pressure ventilation (the arrangement being that the device cannot start until the ventilation has started and 10 volumes of air have been purged from the enclosure) or be totally enclosed filled with inert gas. There is also a requirement for the type submerged in a liquid.
(B) Class I, Division 2. In this location you can have open or nonexplosion-proof enclosed motors if they do not have brushes, switching mechanisms, or arc-producing devices. If they do have brushes, switching mechanisms, or arc-producing devices, the motor or generator must be identified for Class I, Division 1, locations or the devices must be in Class I, Division 1 identified enclosures as per Section 501.105(B). A requirement is noted for the surface temperature of space heaters used to prevent condensation. There are other specific requirements.
501.130 |
Luminaires (Lighting Fixtures) |
(A) Class I, Division 1. The entire fixture assembly must be identified for a Class I, Division 1 location and be protected against physical damage. Pendant luminaires (fixtures) must be wired and hung through rigid metal conduit or threaded steel intermediate conduit. Stems longer than 300 mm (12 in.) must have additional lateral bracing not more than 300 mm (12 in.) from the end of the stem or a flexible fitting approved for a Class I, Division 1 location. All boxes, fittings, etc., must be identified for Class I, Division 1 locations.
(B) Class I, Division 2. Portable lighting equipment must comply with Class I, Division 1 requirements. There is an exception when it is mounted on a moveable stand and connected by flexible cord. Fixed lighting must be protected against physical damage. If there is danger of falling sparks or hot metal igniting vapors or gases, proper enclosures must be provided. If the operating temperature will exceed 80% of the ignition temperature of the gases or vapors, they must comply with Section 501.130(A)(1) or be of the type that has been tested to determine the temperature range or operating temperature marked. Pendant luminaires (fixtures) have the same rules as Class I, Division 1 locations. Switches must be in accordance with Section 501.6(B)(1). Starting equipment for electric-discharge lamps must be in accordance with Section 501.7(B) unless it is part of a "thermally protected fluorescent lamp ballast" and the lighting fixture has been identified for this location.
501.135 |
Utilization Equipment |
501.140 |
Flexible Cords, Class I, Divisions 1 and 2 |
These are permitted only to connect the portable equipment to the fixed part of the system. They can also be used under certain conditions where a greater degree of movement is needed. As such, they must be identified for extra hard usage, contain a grounding conductor, be connected to the supply conductors or terminals in an approved way, ensure that there is no tension applied, and be provided with seals where necessary. Exceptions are made in Sections 501.10(B) and 501.105(B)(6). There is additional information concerning electrical submersible pumps and electric mixers.
501.145 |
Receptacles and Attachment Plugs, Class I, Divisions 1 and 2 |
Must be of the grounding type and approved for Class I locations except as provided in Section 501.105(B)(6).
501.150 |
Signaling, Alarm, Remote-Control, and Communication Systems |
Article 90 Introduction
General
Wiring and Protection
Wiring Methods and Materials
Equipment for General Use
Special Occupancies
Special Equipment
Special Conditions
Tables
Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size
Annex D. Examples
Annex E. Types of Construction