Article 280 Surge ArrestersI. General
II. Installation
III. Connecting Surge Arresters
|
Article 285 Transient Voltage Surge Suppressors (TVSSs)I. General
II. Installation
III. Connecting Transient Voltage Surge Suppressors
|
3. Wiring Methods and Materials
Article 300: Wiring Methods Article 310 Conductors for General Wiring Article 312 Cabinets, Cutout Boxes, and Meter Socket Enclosures Article 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures Article 320 Armored Cable Type AC Article 322 Flat Cable Assemblies Type FC Article 324 Flat Conductor Cable Type FCC Article 326 Integrated Gas Spacer Cable Type IGS Article 328 Medium-Voltage Cable Type MV Article 330 Metal-Clad Cable Type MC Article 332 Mineral-Insulated, Metal-Sheathed Cable Type MI Article 334 Nonmetallic-Sheathed Cable Types NM, NMC, and NMS Article 336 Power and Control Tray Cable Type TC Article 338 Service-Entrance Cable Types SE and USE Article 340 Underground Feeder and Branch-Circuit Cable Type UF Article 342 Intermediate Metal Conduit Type IMC Article 344 Rigid Metal Conduit Type RMC Article 348 Flexible Metal Conduit Type FMC Article 350 Liquidtight Flexible Metal Conduit Type LFMC Article 352 Rigid Nonmetallic Conduit Type RNC Article 353 High Density Polyethylene Conduit Type HDPE Conduit Article 354 Nonmetallic Underground Conduit with Conductors Type NUCC Article 356 Liquidtight Flexible Nonmetallic Conduit Type LFNC Article 358 Electrical Metallic Tubing Type EMT Article 360 Flexible Metallic Tubing Type FMT Article 362 Electrical Nonmetallic Tubing Type ENT Article 366 Auxiliary Gutters Article 374 Cellular Metal Floor Raceways Article 380 Multioutlet Assembly Article 382 Nonmetallic Extensions Article 384 Strut-Type Channel Raceway Article 386 Surface Metal Raceways Article 388 Surface Nonmetallic Raceways Article 390 Underfloor Raceways Article 392 Cable Trays Article 394 Concealed Knob-and-Tube Wiring Article 396 Messenger Supported Wiring Article 398 Open Wiring on Insulators |
Article 300: Wiring MethodsI. General Requirements
This article applies to all wiring installations except as noted in other articles. It does not apply to integral
Table 300.1(C). Metric Designator and Trade Sizes
This chapter applies to voltages up to and including 600 V when not
(A) Single Conductors. The single conductors that are specified in Table 310.13 can be installed only as part of a recognized wiring method described in Chapter 3. Single overhead conductors are permitted if installed in accordance with 225.6.
(B) Conductors of the Same Circuit.
All conductors of the same circuit including the grounded conductor and equipment
(C) Conductors of Different Systems
Reference should be made to this section in the NEC for a complete explanation.
(A) Minimum Cover Requirements. The cover requirements for direct buried cable or conduit are shown in Table 300.5. The reader should refer to it. (B) Listing
(C) Underground Cables under
(D) Protection from Damage (E) Splices and Taps (F) Backfill (G) Raceway Seals (H) Bushing (I) Conductors of the Same Circuit (J) Ground Movement (K) Directional Boring
Generally, all material used must be suitable for use in the installed environment.
(A) Ferrous Metal Equipment.
Ferrous material must be protected both inside and out by a coating of corrosion-resistant material. If corrosion protection is required and threading takes place in the field, then the threads must be coated with an identified electrical conductive, corrosion-resistant compound. Stainless
(B) Non-Ferrous Metal Equipment. Non-ferrous material must have supplementary corrosion protection if embedded in or encased in concrete or in direct contact with the earth.
(C) Nonmetallic Equipment.
Nonmetallic equipment must be made of material approved for the conditions in which it is installed. If exposed to sunlight then the material must be listed as sunlight resistant or be identified as sunlight resistant. If exposed to chemicals or their vapors, the material must be
(D) Indoor Wet Locations. The cable must be installed with at least 6 mm (¼ in.) of air space from the wall or supporting surface when installed exposed. There is an exception.
There must be electrical continuity between all metal race-ways, cable
Splices or taps are not permitted within a raceway. Exceptions to this are noted in Sections 300.15; 368.8(A); 376.56; 378.56; 384.56; 386.56; 388.56; or 390.6. In a multiwire branch circuit the continuity cannot depend on device connections that can be removed.
At least 150 mm (6 in.) of conductors must be left at every outlet, junction, or switch point for splices or connections. When the opening to the point of connection is less than 200 mm (8 in.), the conductors must extend at least 75 mm (3 in.).
{% if main.adsdop %}{% include 'adsenceinline.tpl' %}{% endif %} For concealed knob and tube wiring a box must be installed at each switch point and outlet. Use fittings and connectors only for the purpose that they are listed and designed for. If the wiring method is conduit, tubing, Type AC cable, Type MC cable, Type MI cable, non-metallic sheathed cable or other cables, then a conduit body or box must be installed at each conductor splice point, switch point, outlet point, termination point, pull point and junction point. This requirement for the use of a conduit body or box is in force unless not required by (A) through (M) following. (A) Wiring Methods With Interior Access. If the outlet method has a removable cover that is accessible after installation.
(B) Equipment.
A wiring
(C) Protection. If the cables enter or leave conduit or tubing that is used for support or protection against physical damage. There are requirements for the use of fittings. (D) Type MI Cable. If accessible fittings are used for straight through splices. (E) Integral Enclosure. A wiring device with an integral enclosure that has brackets that fasten it to wall or ceilings for use with nonmetallic sheathed cable is permitted. (F) Fitting. A fitting can be used instead of a conduit body or box as long as there are splices or terminations in the fitting. The fitting has to be accessible after the installation. (G) Direct-Buried Conductors. As permitted in 300.5(E).
(H)
(I) Enclosures.
Where a splice, switch terminal, or pull point is in a cabinet or cut out box in an enclosure for a switch or
(J) Luminaires (Fixtures). If the fixture is used as a raceway as permitted in 410.31 and 410.32. (K) Embedded. Where conductors are embedded as permitted in 424.40, 424.41(D), 426.22(B), 426.24(A), and 427.19(A) they are not required for splices. (L) Manholes and Handhole Enclosures. If only qualified persons have access in manholes except when connecting to electrical equipment and compliance with Part V of Article 110 for manholes and 314.30 for handhole enclosures. (M) Closed Loop. If a device is identified and listed for installation without a box and is used with a closed loop power distribution system.
In general, the number and size of conductors in a raceway must allow the dissipation of heat, easy installation, and withdrawal.
Raceways other than exposed raceways or busways that have hinged or removable covers must be installed complete between outlet, junction, or splicing points before the conductors are installed. Three exceptions are: (1) for prewired assemblies, (2) when necessary for the installation of utilization equipment, and (3) short sections used for protection from physical damage. There is a restriction on the use of
Conductors must be supported at the top of vertical risers with additional support as noted in Table 300.19(A) of the NEC when the rise is greater than the values in that table.
The effects of induced currents in metal enclosures must be minimized. This is done by grouping all phases, neutral, and grounding conductors in one raceway. If individual conductors are used, a slot can be cut between the holes made in the metallic enclosure through which the individual conductor
(A) Ducts for Dust, Loose Stock, or Vapor Removal.
Wiring of any type is
(B) Ducts or Plenums Used for Environmental Air.
The following can be used when the duct or plenum was specifically made for this purpose: Type MI, Type MC cable with the specified sheath, EMT flexible metallic tubing, intermediate metal conduit, or rigid metal conduit. When necessary to connect physically adjustable items, flexible metal conduit can be used, but only in lengths not longer than 1.2 m (4 ft.). Only devices that act on or sense the contained air, such as thermostats, are permitted. If lighting fixtures are installed for maintenance or repair, they must be of the
(C) Other Space Used for Environmental Air.
This paragraph applies to spaces other than those in Sections 300.22(A) and (B) for environmental air handling. Habitable rooms or areas of buildings which are not primarily used for air handling are not included. Only totally enclosed nonventilated insulated busways that do not have a provision for plug-in connections and Type MI cable, Type MC cable without an overall nonmetallic covering, as well as Type AC cable or other factory-
(D) Information Technology Equipment. Refer to Article 645.
II. Requirements for Over 600 Volts, Nominal
See Section 300.3(C)(2).
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||