The dwelling has a floor area of 1500 square feet exclusive of an unfinished cellar not adaptable for future use, unfinished attic, and open porches. It has a 12-kW range, a 2.5-kW water heater, a 1.2-kW dishwasher, 9 kW of electric space heating installed in five rooms, a 5-kW clothes dryer, and a 6-ampere, 230-volt room air-conditioning unit. Assume range, water heater, dishwasher, space heating, and clothes dryer kW ratings equivalent to kVA.
Air conditioner kVA calculation is 6A x 230V ÷ 1000 = 1.38 kVA
This 1.38 kVA [Item 1 from 220.82(C)] is less than 40% of 9 kVA of separately controlled electric heat [Item 6 from 220.82(C)], so the 1.38 kVA need not be included in the service calculation.
General Load |
|
---|---|
1500 sq. ft. at 3 volt-amperes |
4500 VA |
Two 20-amp. appliance outlet circuits at 1500 volt-amperes each |
3000 VA |
Laundry circuit |
1500 VA |
Range (at nameplate rating) |
12,000 VA |
Water heater |
2500 VA |
Dishwasher |
1200 VA |
Clothes dryer |
5000 VA |
Total |
29,700 VA |
Application of Demand Factor [See 220.82(B)]
First 10 kVA of general load at 100% |
= 10,000 VA |
Remainder of general load at 40% (19.7 kVA x .4) |
= 7880 VA |
Total of general load |
= 17,880 VA |
9 kVA of heat at 40% (9000 VA x .4) |
= 3600 VA |
Total |
= 21,480 VA |
Calculated load for service size
Therefore, the minimum service size would be 100 amperes in accordance with 230.42 and 230.79.
Feeder Neutral Load (per 220.61) |
|
---|---|
1500 sq. ft. at 3 volt-amperes |
4500 VA |
Three 20-amp. circuits at 1500 volt-amperes |
4500 VA |
|
9000 VA |
3000 volt-amperes at 100% |
3000 VA |
9000 VA - 3000 VA = 6000 volt-amperes at 35% |
2100 VA |
|
5100 VA |
Range8 kVA at 70% |
5600 VA |
Clothes dryer5 kVA at 70% |
3500 VA |
Dishwasher |
1200 VA |
|
15,400 VA |
Calculated Load for Neutral
Article 90 Introduction
General
Wiring and Protection
Wiring Methods and Materials
Equipment for General Use
Special Occupancies
Special Equipment
Special Conditions
Tables
Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size
Annex D. Examples
Annex E. Types of Construction