I. General
426.1 |
Scope |
This article covers installations both embedded and exposed.
426.2 |
Definitions |
426.3 |
Application of Other Articles |
426.4 |
Continuous Load |
This is to be considered a continuous load.
II. Installation
426.10 |
General |
426.11 |
Use |
426.12 |
Thermal Protection |
Must be protected against contact by persons if operated at temperatures above 60°C (140°F).
426.13 |
Identification |
Warning signs must be posted where used.
426.14 |
Special Permission |
III. Resistance Heating Elements
426.20 |
Embedded De-icing and Snow-Melting Equipment |
Units cannot exceed 1300 watts/m2 (120 W per square foot) and must have at least 25 mm (1 in.) between cables. They can be installed either on an asphalt or masonry base at least 50 mm (2 in.) thick and covered with at least 38 mm (1½ in.) of asphalt or masonry, or on any approved type of base embedded in 90 mm (3½ in.) of asphalt or masonry and covered with at least 38 mm (1½ in.) of asphalt or masonry. They must be secured and not bridge expansion joints unless proper provisions are made.
426.21 |
Exposed De-icing and Snow-Melting Equipment |
They must be secured, proper temperature limiting, and have no cross-bridge expansion joints unless provided for.
426.22 |
Installation of Nonheating Leads for Embedded Equipment |
426.23 |
Installation of Nonheating Leads for Exposed Equipment |
426.24 |
Electrical Connection |
426.25 |
Marking |
426.26 |
Corrosion Protection |
426.27 |
Grounding Braid or Sheath |
426.28 |
Equipment Protection |
IV. Impedance Heating
426.30 |
Personnel Protection |
426.31 |
Isolation Transformer |
426.32 |
Voltage Limitations |
The secondary winding of the isolation transformer must not operate at greater than 30 V ac unless protected by a ground fault circuit interrupter. If ground fault circuit interrupter is used it can be greater than 30 V but not more than 80 V.
426.33 |
Induced Currents |
426.34 |
Grounding |
V. Skin Effect Heating
426.40 |
Conductor Ampacity |
426.41 |
Pull Boxes |
426.42 |
Single Conductor in Enclosure |
426.43 |
Corrosion Protection |
426.44 |
Grounding |
VI. Control and Protection
426.50 |
Disconnecting Means |
Must have a disconnecting means that opens the ungrounded wires. The branch-circuit breaker can be used if readily accessible. Also permitted is a factory-installed attachment plug if it is rated not more than 20 A and 150 V to ground.
426.51 |
Controllers |
If the temperature controller operates line current and has an off position, it must open all ungrounded conductors. It cannot be used as a disconnecting means unless it can be locked in the open position. If no off position is provided, it does not have to open all ungrounded conductors and cannot be used as a disconnecting means. If it controls a relay, it does not have to open all ungrounded conductors and cannot be used as a disconnecting means. There are also rules in the NEC® for combined switching devices.
426.52 |
Overcurrent Protection |
Refer to Section 426.4.
426.54 |
Cord- and Plug-Connected De-icing and Snow Melting Equipment |
Article 90 Introduction
General
Wiring and Protection
Wiring Methods and Materials
Equipment for General Use
Special Occupancies
Special Equipment
Special Conditions
Tables
Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size
Annex D. Examples
Annex E. Types of Construction