Flylib.com

Books Software

 
 
 

HVAC Zones


HVAC Zones

Creating HVAC zones in a house can save energy as well as better serve the heating and cooling needs of different areas of the house. Many people confuse zones with independent systems where each area has a separate HVAC system. Zoning a house involves the design and installation of a series of airflow dampers that control the ambient temperature separately from other zones or areas of the house using a single HVAC system.

A single zone system or, in other words, a single HVAC system doesn’t require damper systems; the whole house is a single zone with one ambient heating and cooling environment. A multizone HVAC system has at least two airflow dampers, with each damper managing the airflow into one specific zone and independently controlled by a thermostat .

Zoning is recommended in homes that have any of the following characteristics:

  • Multiple levels or floors

  • A widespread design, such as homes with separate building wings or large ranch-style layouts

  • Rooms with large window surfaces

  • Large open architecture areas with vaulted or cathedral ceilings, an atrium, or a solarium

  • Living space in a finished basement or attic

  • Rooms with exposed concrete flooring (such as in a basement)

  • An indoor swimming pool or spa

  • Earth-shelter houses that have only one or two exterior walls

HVAC Zone Controllers

A standard HVAC system typically has a single thermostat that controls the heating and cooling for an entire house. A zone control system connects two or more thermostats to a single HVAC system. The thermostats aren’t the zone controllers; rather, there is a master zone control device that is connected to the thermostats in each zone, the HVAC system, and each airflow damper.

The master zone controller reacts to the set points of the zone thermostats and opens or closes the dampers, which are located inside the source HVAC ducts leading to each zone. In their normal state, the dampers are open, but the controller can shut them to close off the flow of heating or cooling to a zone.

The zone thermostat operates normally to call for heating or cooling according to its set points. However, the zone thermostat signals actually go to the master zone controller that controls the HVAC system and adjusts the dampers according to the zone settings.

The criteria for selecting a zone controller, such as the unit shown in Figure 29-7, are the number of zones, the type of HVAC system in use, and the size of the house. The size of the house is especially important, as is if the house has more than one story or levels, such as a two-story, three-story, or a tri-level house. In these situations, the master zone control unit should include a thermal equalization capability that balances the ambient temperature of the different levels.

click to expand
Figure 29-7: An HVAC zone control unit

Photo courtesy of Residential Control Systems, Inc.

HVAC Zone Design

HVAC zoning is very difficult to add to an existing HVAC system, so for the most part, zoning is a new construction application. Not many home automation firms take on the job of designing the actual HVAC system, the ductwork, or the location of the airflow registers, so leave this part of the job to the HVAC and mechanical engineering people.

Once the HVAC system is designed, the design of the HVAC zoning can be done using the following steps:

  1. Establish the number of zones.   Typically, a two- (or more) story house has at least two zones, but the goal is to establish HVAC zones that are roughly the same size in area. The zones shouldn’t be too small because they will be difficult to control, or too large because they may be subject to cold or hot spots. A zone should be created for each separate climatic environment the homeowner desires, typically defined by the activities of the area. For example, a family room where the occupants may be more active can be slightly cooler than a living room where the occupants are less active.

  2. Adjust the HVAC duct plan to fit the zone design.   Ductwork must be designed so that each zone is a separate branch of the main HVAC duct system. The damper for each zone will be installed just after a zone’s ducts branch from the main duct. The volume of the ductwork branches may need to be increased to handle an increased airflow volume. Work with the HVAC specialists to design the volume of the ductwork for a system that is open all the time. Each duct in the system should be able to handle the entire airflow volume of the HVAC system. This allows the system to function normally, even when a damper is closed, without putting too much back pressure on the HVAC system and possibly damaging it. The general rule-of-thumb for increasing the size of the ductwork is to add an additional 25 percent of volume for every two zones on the system. For example, a two-zone system should be increased 25 percent; a four-zone system should be increased 50 percent; and so on.

  3. Establish the location of the dampers and thermostats.   During the pre-wire stage, run two-conductor thermostat wire to the damper locations and five to seven conductor thermostat wire to the thermostat locations. If you are using remote temperature sensors with the system, that wiring must be installed as well.

Zoning Hydronic Systems

Hydronic systems are generally zoned by default, but if you wish to be able to turn the heat on or off in different areas of a home, control valves must be installed in the hydronic piping in the same way that dampers are installed in the air ducts of a forced air system.

Hydronic valves (see Figure 29-8) are motorized to open and close according to the commands of the master zone controller. They open and close the flow of water through the hydronic system.

click to expand
Figure 29-8: A hydronic motorized value

Photo courtesy of Invensys Building Systems, PLC.

Locating a Thermostat

For the best results, a thermostat should be located on an inside wall in an area that is frequently occupied. The thermostat should be at least 18 inches from any outside walls and at least 5 feet above the floor. It should also be placed in an area with freely circulating average temperature air. A thermostat should not be located in any of the following areas:

  • On an outside wall

  • In direct sunlight or near any heat produced by any closely placed appliances

  • Near or in line with a heating or air conditioner vent, a stairwell, or an outside door

  • Near any device that produces electrical interference

    Note 

    Some thermostats are “power-stealing” units. This type of thermostat takes power from the “W” (see Table 29-1 later in the chapter) heat connection running from the HVAC system. If multiple zone control units are also being installed, don’t connect a power stealing unit or an older style mechanical or anticipator type thermostat to the controller. Neither of these thermostats will work properly with an HVAC control unit.

Wiring a Thermostat

The wiring used to connect a thermostat to the HVAC systems must be no less than 20-gauge wire, and for wire runs longer than 100 feet, 18-gauge wire is highly recommended. Thermostat wiring is different from other wire, such as Cat 3 or 5, audio/video, or speaker wiring. Thermostat wiring has two to seven conductors (see Figure 29-9) of solid core wiring with the color -coding for a seven-wire cable consisting of white, red, green, blue, yellow, brown, and orange. Most HVAC central unit controls, which the thermostat wire connects to, use from five to seven conductors. However, in new construction situations, installing seven-conductor thermostat wire adds to the future proofing of the house.


Figure 29-9: Examples of two- and five-conductor thermostat wiring

Standard HVAC Thermostat   Typically, the HVAC technicians install the wiring for a central-system thermostat at the time the HVAC systems are installed. The wiring for the thermostat normally is either two- or four-conductor wiring to support either 24V or 120V systems, depending on the needs of the HVAC system and the thermostat planned into the HVAC system. If the plan is for the home system technician to install a standard thermostat, you will need to follow the thermostat manufacturer’s wiring diagram. Figure 29-10 shows an example of a wiring diagram for a typical nonautomated, or noncommunicating, thermostat.

click to expand
Figure 29-10: A sample wiring diagram for a standard thermostat

When connecting the thermostat wire to the thermostat terminals (see Figure 29-11), strip about ¼-inch of the insulation at the end of each conductor. On most standard thermostats, the terminals are marked with either stickers or embossed letters in the thermostat’s plastic that indicate which wire color should be connected to which terminal. Wrap the exposed end of the conductor wire clockwise around the terminal screw. The manufacturer’s wiring diagram and documentation should also have these details.


Figure 29-11: Installing the wiring on a standard thermostat device

Note 

Of course, you already know that regardless of the type of wiring in use for the thermostat, you should turn off the power at the AC circuit breaker panel before beginning to attach the wire to the thermostat.

Remote Controlled Communicating Thermostat   It is more likely that if the system installation plans for a home include the home technology technicians installing a thermostat, the thermostat is one that can be remotely controlled by some form of remote control unit and is able to communicate with a central home system control unit either with radio frequency (RF) or PLC signals.

The basic wiring for a remotely controlled thermostat is typically very similar to that of a standard thermostat. However, additional installation steps are usually required to accommodate its communications functions.

If the thermostat uses RF signals to communicate to a receiver module located near the HVAC equipment or a home system controller, follow the manufacturer’s guidelines for range and placement in a room. For example, most manufacturers recommend that an RF thermostat be place at least five feet from the floor and not behind a door or other large object in a room.

If the thermostat uses PLC signals to communicate to a home system control unit, at least two devices must be installed and possibly three. This includes one or more wall display units and a control module that serves as an interface between the display units and either the HVAC system (see Figure 29-12) or the home system control unit, and possibly a separate communications module for remote control access. Figure 29-13 shows the modules of a three-part PLC thermostat system.

click to expand
Figure 29-12: An illustration of the general installation of a PLC thermostat

click to expand
Figure 29-13: The components of a PLC remote control thermostat system, with the controller (left), thermostat (center), and the PLC module (right)

Photo courtesy of Smarthome, Inc.

Rough-In   If the HVAC wiring is going in before the HVAC system, meaning the central HVAC system, first identify the location of the HVAC system. In most houses, the HVAC system is either in a basement, garage, or utility closet. To help with interfacing to the HVAC system, install a low-voltage box on a stud near where the HVAC system will sit. Locate the outlet box so that it is accessible for wiring and hookup. One idea is to place it one foot above the floor (measured to the center of the box). You should leave eight to ten feet of thermostat wire available to later wire the thermostat to the HVAC control.

At the spot where each thermostat will be installed during trim out, leave about one foot of wire slack to connect to the thermostat. During trim out and before the thermostat is attached to the wall and connected to the wire, be sure to seal around the hole the wire is passed through to avoid cold or warm air from the wall effecting the performance of the thermostat.

When pre-wiring for the HVAC control, run the wire from the thermostat and route it by the HVAC system unit (in an outlet box with an eight to ten foot loop) and on to the home control unit. It is a good idea to always prewire for HVAC control, even if not desired initially by the homeowner. By installing the wiring now, it is easy to add HVAC control in the future.

HVAC systems have two levels of wiring: line voltage and low voltage. Line voltage wiring supplies power to the components of the HVAC system, including its condenser, fan, furnace , or boiler. An electrician typically installs line voltage lines. Low voltage wiring for an HVAC system includes the thermostats, zone controls, any relay or control modules, and the control wiring for the system.

Typically, the wire installed for the HVAC control links should be a shielded wire with conductors of not less than American Wire Gauge (AWG) 14. Many local electrical codes require that control wiring be twisted as pairs and referenced to a particular wire type and manufacturer, such as Belden 8760 (single shielded twisted pair) or 8770 (three-conductor shielded twisted resistance temperature devices [RTD]  cable). In addition to the shielding on the cable, control wiring should be installed at least a distance of 12 inches from power lines.

At the location of the thermostat, label each wire with the letter code assigned to the terminals of the HVAC system and the thermostat using cable marking tape or masking tape. Label both ends of the cable to ensure conformity . Table 29-1 lists the terminal codes most commonly used in the more popular heating systems. Not every system will have every one of the codes included in Table 29-1 and, in some cases, they may substitute or reassign a wire color or terminal code to another function. Be sure to review the system wiring documentation before labeling the wires to ensure the wires are properly labeled at each end.

Table 29-1: Commonly Used HVAC Terminal Codes

Terminal Designation

Wire Color

Application

B

Blue or orange

Switch reversing valve on heat pump to heat

C

Blue, brown, or black

Transformer common

E

Blue, pink, gray, or tan

Heat pump emergency heat relay (not commonly used)

G

Green

Furnace fan

L

Blue, brown, tan, or gray

Service indicator light

O

Orange

Switch reversing valve on heat pump to cool

R

Red

Transformer–hot lead

T

Tan or gray

Outdoor anticipator reset

W

White

Heat

X

Blue, brown, or black

Transformer common

Y

Yellow

Cooling compressor

Note 

Heat pumps have two stages of heating and cooling, while standard gas or electric HVAC systems have only a single stage of heating or cooling.