Article 504 Intrinsically Safe SystemsArticle 505 Class I, Zone 0, 1, and 2 Locations
If this article is used, the equipment selection, wiring
Article 506 Zone 20, 21, and 22 Locations for Flammable Dusts, Fibers, and Flyings
Article 510 Hazardous (
|
|
517.1 |
Scope |
Electrical construction and installation criteria for health care facilities that provide service to human beings are covered in this article. Performance, maintenance, and testing criteria are covered in NFPA 99 and other appropriate health care documents. Veterinary facilities are not covered. The reader is referred to NFPA 99.
Parts II and III are intended to be applied to both single-function buildings and to
|
517.2 |
Definitions |
Many definitions are listed in this section that are not covered in Article 100. These are specific to health care facilities. The reader should refer to these in the Code.
|
517.10 |
Applicability |
Generally, this part applies to all health care facilities. Part II does not apply to business offices, corridors, waiting rooms, and similar areas in clinics, medical and dental offices, and outpatient clinics, and if wired in accordance with Chapters 1, 2, 3, and 4 of the Code, patient sleeping areas in nursing
|
517.11 |
General Installation-Construction Criteria |
It is important that the system installed maintain low potential differences between exposed conductive surfaces which are likely to become energized and the patient could contact.
|
517.12 |
Wiring Methods |
All the requirements of Chapters 1 through 4 must be followed unless they are changed in this article.
|
517.13 |
Grounding of Receptacles and Fixed Electric Equipment in Patient Care Areas |
(A) Wiring Methods.
Branch circuits serving patient care areas must have a ground
(B)
|
517.14 |
Panelboard Bonding |
The equipment grounding
|
517.16 |
Receptacles with Insulated Grounding Terminals |
|
517.17 |
Ground-Fault Protection |
(A) Applicability. Hospitals and other buildings that have or provide essential utilities or services for critical care areas or use life support equipment must comply with 517.17.
(B) Feeders.
If ground-fault protection is used at the service disconnect as per Section 230.95 or 215.10, an additional step is needed at the
(C) Selectivity. The system must be fully selective. Six-cycle separation between the levels is required.
(D) Testing
|
517.18 |
General Care Areas |
(A) Patient Bed Location. Each patient bed location must have at least two branch circuits, at least one of them must originate from the normal system and one from the emergency system. All branch circuits on the normal system must come from the same panel-board. There are three exceptions to this.
(B) Patient Bed Location Receptacles. Each location must have at least four receptacles, either single, duplex, or a combination. They must all be hospital grade and grounded with an insulated copper conductor in accordance with Table 250.122. There are two exceptions to this.
(C) Pediatric Locations. The receptacles must be listed tamper resistant or have a listed tamper resistant cover.
|
517.19 |
Critical Care Areas |
(A) Patient Bed Location Branch Circuits.
Each patient bed location must have at least two branch circuits, at least one from the normal system and one from the emergency system. One circuit on the emergency system that
(B) Patient Bed Location Receptacles. Each location must have at least six receptacles, either single, duplex, or a combination of both. At least one must be connected to the normal system or an emergency system supplied by a different transfer switch than the other receptacles in that location. They must all be hospital grade and grounded with an insulated copper conductor to the reference grounding point.
(C) Patient Vicinity Grounding and Bonding (Optional).
A patient equipment grounding point is allowed in the patient vicinity. It can have grounding and bonding
(D) Panelboard Grounding.
Grounding of panelboards and
(E) Additional Protective Techniques in Critical Care Areas (Optional). Isolated power systems are permitted.
(F) Isolated Power System Grounding
(G) Special-Purpose Receptacle Grounding
|
517.20 |
Wet Locations |
(A) In a wet location two methods can be used to protect personnel. Either a ground-fault circuit interrupter can be used if power interruption is acceptable or an isolated power supply can be used. There is an exception.
(B) Isolated power supplies must conform to Section 517.160.
|
517.21 |
Ground-Fault Circuit Protection for Personnel |
Not required for receptacles in critical care areas that have the
|
517.25 |
Scope |
This system is needed to provide light and power for systems essential to life safety and orderly cessation of procedures during a power failure of the normal electrical supply. The types of structures and services are listed in the Code. The reader is also referred to NFPA 99-2002 for further information as to the need for an essential electrical system.
|
517.26 |
Application of Other Articles |
|
517.30 |
Essential Electrical Systems for Hospitals |
(A) Applicability
(B) General. The system is comprised of two separate systems, the emergency system and the equipment system. The emergency systems has a life safety branch and a critical branch. The equipment system supplies power to major equipment. The number of transfer switches depends on many design considerations. One switch can be used for a system with a maximum demand of 150 kVA (120 kw). Loads not noted in Article 517 must have their own transfer switch and must not transfer if it overloads the generator and must automatically shed if the generating equipment becomes overloaded. Continguous facilities can be served by the hospital power and alternate power sources. [NFPA99, 13.3.4.3]
(C) Wiring Requirements. The life safety and critical branch must be kept separate from all other wiring and equipment except for four conditions. The wiring of the emergency system must be mechanically protected. There are five methods accepted. When isolated power systems are used in anesthetizing locations or special environments, each must be supplied by a separate circuit.
(D) Capacity of Systems. The system must be able to supply the entire load. There is now a statement on demand calculations.
(E) Receptacle Identification.
Must be distinctively
|
517.31 |
Emergency System |
This is divided into two required branches, the life safety and the critical. This system must be automatically restored to power within 10 seconds of the loss of the normal supply. [NFPA99, 4.4.2.2.2.1, 4.4.3.1]
|
517.32 |
Life Safety Branch |
The Code lists all the items that are required to be on the life safety branch. They are basically
|
517.33 |
Critical Branch |
The Code lists all the items that are required to be on the critical branch. They are basically task illumination and selected receptacles for the isolated power system, anesthetizing locations, patient care areas, additional specialized areas, nurse call systems, blood, bone and
|
517.34 |
Equipment Source Connection to Alternate Power Source |
This section describes what equipment must be placed on the equipment system. It also describes how the system is energized (i.e., automatic, delayed automatic, and manually). The reader is referred to the Code for the exact requirements.
|
517.35 |
Sources of Power |
(A) Two Independent Sources of Power.
There must be a normal source of power and an alternate source of power for use when the normal source is
(B) Alternate Source of Power. This must be located on the premises and be a generator driven by a prime mover, another generator when the normal source is a generator, or an outside utility company when the normal source is a generator.
(C) Location of Essential Electrical System Components
|
517.40 |
Essential Electrical Systems for Nursing Homes and Limited Care Facilities |
(A) Applicability
(B) Inpatient Hospital Care Facilities. If the facility provides inpatient hospital care, it must comply with the requirements of Part III, 517.30 through 517.35.
(C) Facilities Contiguous with Hospitals. These can have their systems supplied by the hospital. The reader is again referred to NFPA 99-2002 for performance, maintenance, and testing requirements.
|
517.41 |
Essential Electrical Systems |
(A) General. The systems for nursing homes and limited care facilities must have two separate branches, the life safety branch and the critical branch. [NFPA99, FPN ANNEX A 4.5.2.2.1]
(B) Transfer Switches. The number of transfer switches depends on design. One transfer switch is permitted if the load is not more than 150 kVA. [NFPA99, 4.5.2.2.1]
(C) Capacity of System. The system must be capable of supplying the entire load, that is required on the essential electrical system.
(D) Separation from Other Circuits. The life safety branch must be kept separate from all other wiring and equipment. There are three exceptions.
(E) Receptacle Identification.
The receptacles or cover plates must have a
|
517.42 |
Automatic Connection to Life Safety Branch |
The life safety branch must be automatically restored to power after 10 seconds of loss of the normal source of supply. This branch is referred to as the emergency system in NFPA 99-2002. The life safety branch basically supplies power for illumination of means of egress, exit signs, alarm and alerting systems, communication systems, dining and recreation areas, generator set location, and elevators. Refer to the Code for complete requirements. No function other than those listed can be connected to the life safety branch. For elevators [NFPA99, 4.4.2.2.2.2(6) and 4.5.2.2.2(7)]
|
517.43 |
Connection to Critical Branch |
This section describes what must be connected to the critical branch and how it is to be energized from the essential electrical system (i.e., automatic, delayed automatic, or manual).
|
517.44 |
Sources of Power |
(A) Two Independent Sources of Power. There must be a normal source of power and an alternate source of power for use when the normal source is interrupted. [NFPA99, 4.4.1.1.4]
(B) Alternate Source of Power. This must be located on the premises and be a generator driven by a prime mover. There is an exception to this when the normal source is a generator. In that case the alternate source can be either another generator or an outside utility company. There is also an exception where battery units may be used in nursing homes or limited-care facilities meeting the requirements of Section 517.40(A), Exception. [NFPA99, 17.3.4.1, 18.3.4.1.1]
(C) Location of Essential Electrical System Components
|
517.45 |
Essential Electrical Systems for Other Health Care Facilities |
(A) Essential Electrical Distribution. A battery or generator system must be used for the essential electrical distribution system. [NFPA 99-2002]
(B) Electrical Life Support Equipment. An essential electrical distribution system described in 517.30 through 517.35 must be used if electrical life support equipment is required. [NFPA 99: 14.3.4.2.1]
(C) Critical Care Areas. An essential electrical distribution system as described in 527.30 through 517.35 must be used where critical care areas are located. [NFPA99, 14.3.4.2.2]
(D) Power Systems. Battery systems must follow the requirements of Article 700 and generator systems must follow the requirements of 517.30 through 517.35.
The reader is again referred to NFPA 99-2002.
|
517.60 |
Anesthetizing Location Classification |
These are classified as hazardous (classified) or other-than-hazardous (classified).
|
517.61 |
Wiring and Equipment |
|
517.62 |
Grounding |
|
517.63 |
Grounded Power Systems in Anesthetizing Locations |
|
517.64 |
Low-Voltage Equipment and Instruments |
|
517.71 |
Connection to Supply Circuit |
|
517.72 |
Disconnecting Means |
|
517.73 |
Rating of Supply Conductors and Overcurrent Protection |
|
517.74 |
Control Circuit Conductors |
|
517.75 |
Equipment Installations |
|
517.76 |
Transformers and Capacitors |
|
517.77 |
Installation of High-Tension X-Ray Cables |
|
517.78 |
Guarding and Grounding |
|
517.80 |
Patient Care Areas |
|
517.81 |
Other than Patient Care Areas |
|
517.82 |
Signal Transmission between Appliances |
|
517.160 |
Isolated Power Systems |
(A) Installations
(B) Line Isolation Monitor
The following article titles are listed for reference: Article 518 Assembly Occupancies; Article 520 Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations; Article 525 Carnivals, Circuses, Fairs, and Similar Events; Article 530 Motion Picture and Television Studios and Similar Locations; Article 540 Motion Picture Projection Rooms; Article 545 Manufactured Buildings; Article 547 Agricultural Buildings; Article 550 Mobile Homes, Manufactured Homes, and Mobile Home Parks; Article 551 Recreational Vehicles and Recreational Vehicle Parks; Article 552 Park Trailers; Article 553 Floating Buildings; Article 555 Marinas and Boatyards; 590 Temporary Installations.