Article 353 High Density Polyethylene Conduit Type HDPE Conduit

I. General

353.1

Scope

353.2

Definition

A conduit that is circular in cross section with its associated couplings, connectors, etc. that is nonmetallic and used for the installation of electrical conductors.

353.6

Listing Requirements.

 

II. Installation

353.10

Uses Permitted

In can be used in cinder fill; in continuous lengths from a reel or discrete lengths; in areas that are corrosive as noted in 300.6 and where the conduit is listed for use where subject to certain chemicals; and for direct burial in earth or concrete (refer to 300.5 and 300.50 for underground installations).

353.12

Uses Not Permitted

It cannot be used where exposed; in hazardous (classified) locations unless permitted in 504.20; within a building; in ambient temperatures higher than 50°C (122°F) unless listed for higher; for conductors or cables operating at a higher temperature than the conduit listed operating temperature. There is an exception.

353.20

Size

You cannot use a smaller size than metric designator 16 (trade size ½) or larger than metric designator 103 (trade size 4).

353.22

Number of Conductors

Cannot exceed the percentage fill of Table 1, Chapter 9. Cables can be used if not prohibited by the cable articles. Cable cannot exceed the fill requirements of Table 1, Chapter 9.

353.24

BendsHow Made

They must be manually made and must not be damaged. Refer to Table 354.24.

353.26

BendsNumber in One Run

The maximum that is permitted is not more than 360° in bends between termination points.

353.28

Trimming

Remove rough edges.

353.46

Bushings

A bushing must be used at the point where the conduit goes into a box or fitting unless protection is provided in the box or fitting.

353.48

Joints

Use approved methods.

353.56

Splices and Taps

They are permitted only in accordance with Section 300.15.

353.60

Grounding

A separate equipment grounding conductor must be installed where equipment ground is required. There are two exceptions.

III. Construction Specifications

353.100

Construction

This conduit must be composed of nonmetallic material and must be resistant to moisture and chemical atmospheres. It must be resistant to moisture and corrosive agents. It must be strong enough to withstand abuse during installation. If used for direct burial without being encased in concrete, it must be able to withstand the continued loading after installation.

353.120

Marking

It must be marked at least every 3 m (10 ft.) as noted in 110.21. The marking must include the type of material.

Article 90 Introduction

General

Wiring and Protection

Wiring Methods and Materials

Equipment for General Use

Special Occupancies

Special Equipment

Special Conditions

Tables

Annex C. Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

Annex D. Examples

Annex E. Types of Construction



Pocket Guide to the National Electrical Code 2005